Box-type substations · ZGS11

ZGS11 Combined Transformer Series (American-Style Pad-Mounted Substation)

The ZGS11 combined transformer series, also known as the American-style pad-mounted substation, suits load centres in urban networks, residential districts, hospitals, schools, airports and stations, cutting losses and improving supply quality.

Product overview

ZGS11 combined transformers (American-style pad-mounted), 100–1600 kVA, fully sealed tank and fully insulated design, for ring-main or radial supply.

ZGS11 American-style pad-mounted substation in a green steel enclosure with lockable front doors
Model
ZGS11
Product family
Box-type substations

Overview

The ZGS11 combined transformer (American-style pad-mounted substation) brings the HV load-break switch, back-up fuses, transformer body and LV outgoing unit together in one fully sealed tank. It is small and compact and is used at load centres in urban networks, residential districts, hospitals, schools, airports and stations, reducing losses and improving supply quality.

Features

  • Small size and a rational, compact structure.
  • Fully sealed tank and fully insulated design for safe, reliable operation.
  • High overload capability and excellent withstand against sudden short circuits.
  • Suitable for both ring-main and radial (terminal) supply.
  • Easy to operate, with reliable supply.
  • Energy-efficient, with low losses.
  • Good resistance to impulse stress.
  • Cable connectors switch up to 200 A load current, with long mechanical and electrical life.

Technical specification

  • Rated capacity: 100 to 1600 kVA.
  • Rated voltage: 6 / 6.3 / 6.6 / 10 / 10.5 / 11 kV.
  • Tapping range: ±5% or ±2×2.5%.
  • Vector group: Dyn11.
  • Power-frequency withstand voltage: 25 kV/1 min for the 6 kV class; 35 kV/1 min for the 10 kV class.
  • Impulse voltage: BIL 60 kV for the 6 kV class; BIL 75 kV for the 10 kV class.
  • Back-up fuse breaking capacity: 50 kA.
  • Load-break switch: 300 A; short-time withstand current 12.5 kA for 2 s (ring main) and 16 kA for 1 s (terminal); peak withstand current 31.5 kA (ring main) and 40 kA (terminal).
  • Ambient temperature: -20 °C to +40 °C; top-oil temperature below 85 °C.
  • Noise level: 50 dB or less.

Key features

  • Small size with a rational, compact structure
  • Fully sealed tank and fully insulated design
  • High overload capability, strong short-circuit withstand
  • Suitable for both ring-main and radial supply
  • Low losses, easy operation and reliable supply
  • Good resistance to impulse stress
  • Cable connectors rated for 200 A load switching
  • Capacities from 100 to 1600 kVA, vector group Dyn11
Enquire about this product

Key facts

Rated capacity
100–1600 kVA
HV rating
6–11 kV (6 / 6.3 / 6.6 / 10 / 10.5 / 11 kV)
Degree of protection
to order
Layout
Fully sealed tank, combined pad-mounted design

Technical parameters

ZGS11-H ring-main combined transformer — technical parameters (HV 6 / 6.3 / 10 / 10.5 / 11 kV, tapping range ±5% or ±2×2.5%, LV 0.4 kV, vector group Dyn11)
Rated capacity (kVA)No-load current (%)No-load loss (W)Load loss (W)Impedance voltage (%)
1001.629015004.0
1601.440022004.0
2001.348026004.0
2501.256030504.0
3151.167036504.0
4001.080043004.0
5001.096051504.5
6300.9120062004.5
8000.8140075004.5
10000.71700103004.5
12500.61950128004.5
16000.62400145004.5

Typical installations

  • Urban network load centres
  • Residential districts
  • Hospitals
  • Schools
  • Airports
  • Railway stations
  • Ring-main supply
  • Radial (terminal) supply
Solutions and quotations

Tell us what your project needs

Send the capacity, voltage class and installation conditions, and we will come back with a selection proposal, technical data and a quotation.

  • Amorphous alloy transformers
  • Custom configuration
  • Type-test reports
  • After-sales support