HV & LV switchgear assemblies · GGD
GGD AC Low-Voltage Switchgear
GGD AC low-voltage switchgear serves power plants, substations and industrial and mining users for the conversion, distribution and control of power for drives, lighting and distribution equipment, and replaces earlier generations of low-voltage assemblies.
Product overview
Fixed-type LV switchgear for 50 Hz, 380 V distribution systems up to 3150 A, with high breaking capacity and good dynamic and thermal stability.

- Model
- GGD
- Product family
- HV & LV switchgear assemblies
Overview
GGD switchgear is used by power plants, substations and industrial and mining enterprises in distribution systems at 50 Hz, a rated operating voltage of 380 V and rated currents up to 3150 A, for the conversion, distribution and control of power supplied to drives, lighting and distribution equipment. It offers high breaking capacity, good dynamic and thermal stability, flexible electrical schemes, easy combination, a wide and practical range, a modern structure and a high degree of protection.
Construction
- Rigid frame: the structure is assembled from 8MF cold-formed steel sections with local welding; parts follow a modular design and the frame carries evenly spaced E = 20 mm mounting holes, giving a high degree of standardisation.
- Efficient cooling: ventilation slots at the top and bottom of the enclosure let heat escape through the upper openings while cool air enters below, forming a natural convection duct that solves the cooling problem of enclosed switchgear.
- Earthing: instrument doors carrying components are bonded to the frame with stranded copper braid and a dedicated earthing busbar runs along the base, so the complete cubicle forms an uninterrupted protective earth circuit.
- Easy assembly: the removable top cover simplifies fitting and adjusting the main busbar on site, and four lifting eyes at the top corners ease handling and transport.
- Degree of protection: IP30 as standard, selectable between IP20 and IP40 according to the service environment.
Service conditions
- Ambient temperature: between -5 °C and +40 °C, with a 24-hour average not above +35 °C.
- Altitude: not exceeding 2000 m; above this the assembly must be derated as required by the standard.
- Humidity: relative humidity not above 50% at +40 °C; at lower temperatures (for example +20 °C) the monthly average may reach 90%, so ventilation or heating must be provided against condensation.
- Installation: tilt from the vertical not exceeding 5°; install in a location free from fire and explosion hazards, corrosive gases, conductive dust and severe vibration or shock.
- Special requirements: state highly corrosive atmospheres, high altitudes and similar conditions at the order stage so that special treatment can be applied.
Key features
- High breaking capacity with good dynamic and thermal stability
- 8MF cold-formed steel frame, accurate and rigid
- Modular E = 20 mm mounting holes for standardised production
- Top and bottom ventilation slots form a natural convection duct
- Instrument doors bonded by copper braid; complete earthing circuit
- Removable top cover and four lifting eyes
- IP30 as standard, selectable from IP20 to IP40
Key facts
- Rated voltage
- AC 380 V, 50 Hz
- Rated current
- ≤ 3150 A
- Degree of protection
- IP30 (IP20–IP40 optional)
- Construction
- Fixed type, 8MF cold-formed steel frame
Technical parameters
| Type | Rated voltage (V) | Rated current (A) | Rated short-circuit breaking current (kA) | Rated short-time withstand current (kA) | Rated peak withstand current (kA) |
|---|---|---|---|---|---|
| GGD1 | 380 | A 1000 / B 600(630) / C 400 | 15 | 15 | 30 |
| GGD2 | 380 | A 1500(1600) / B 1000 | 30 | 30 | 63 |
| GGD3 | 380 | A 3150 / B 2500 / C 2000 | 50 | 50 | 105 |
Typical installations
- Power plants
- Substations
- Industrial and mining enterprises
- Power distribution
- Lighting distribution
- Retrofit of low-voltage assemblies
Related products
Other products in this family
GCS
Rated voltage:
AC 380 V / 660 V, 50/60 Hz
Rated current:
≤ 4000 A

GCS AC Low-Voltage Withdrawable Switchgear
Withdrawable LV switchgear assembly for 50/60 Hz, 380/660 V networks up to 4000 A, used for incoming and feeder circuits and centralised motor control.
MNS
Rated voltage:
AC up to 660 V, 50/60 Hz
Rated current:
to order

MNS AC Low-Voltage Withdrawable Switchgear
Modular withdrawable LV switchgear for 50/60 Hz systems up to 660 V, used as a power distribution centre (PC) or a motor control centre (MCC).
GCK
Rated voltage:
AC 380 V, 50–60 Hz
Rated current:
to order

GCK AC Low-Voltage Withdrawable Switchgear
Withdrawable LV switchgear assembly for three-phase 50–60 Hz, 380 V systems, serving as power distribution (PC) and centralised motor control (MCC) equipment.
Solutions and quotations
Tell us what your project needs
Send the capacity, voltage class and installation conditions, and we will come back with a selection proposal, technical data and a quotation.
- Amorphous alloy transformers
- Custom configuration
- Type-test reports
- After-sales support